More than 150 countries customers enjoy the service of kulon

Home > Products > EDR Series >

EDR-120

EDR-120
EDR-120
EDR-120EDR-120EDR-120EDR-120
CategoriesEDR Series
AlbumView larger image
BrandMeanwell Switching Power Supply
ModelEDR-120
Wattage120w
Wattage Input120w
Output(Vdc)12v,24v,48v
PFC-
SafetyUL,CB,CE,TUV,EMC,ACMC,BSMI,EAC
L*W*H40*125*113mm
Warranty2 years
Update Time2020-04-07
Detail Information

120W Single Output Industrial DIN RAIL  EDR-120 series

Feature:

  • Universal AC input / Full range

  • Protections:short circuit/ overload / over voltage / Over temperature

  • Can be installed on DIN rail TS-35/7.5 or 15

  • Cooling by free air convection

  • UL 508(industrial control equipment)approved

  • EN61000-6-2(EN50082-2) industrial immunity level

  • 100% full load burn-in test

  • 2 years warranty

specification:

MODEL EDR-120-12 EDR-120-24 EDR-120-48
OUTPUT DC VOLTAGE 12V 24V 48V
RATED CURRENT 10A 5A 2.5A
CURRENT RANGE 0 ~ 10A 0 ~ 5A 0 ~ 2.5A
RATED POWER 120W 120W 120W
RIPPLE & NOISE (max.) Note.2 100mVp-p 120mVp-p 150mVp-p
VOLTAGE ADJ. RANGE 12 ~ 14V 24 ~ 28V 48 ~ 55V
VOLTAGE TOLERANCE Note.3 ±2.0% ±1.0% ±1.0%
LINE REGULATION ±0.5% ±0.5% ±0.5%
LOAD REGULATION ±1.0% ±1.0% ±1.0%
SETUP, RISE TIME 1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.) 16ms/230VAC 10ms/115VAC at full load
INPUT VOLTAGE RANGE Note.6 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE 47 ~ 63Hz
   
EFFICIENCY (Typ.) 85% 87.5% 88.5%
AC CURRENT (Typ.) 2.25A/115VAC 1.3A/230VAC
INRUSH CURRENT (Typ.) 20A/115VAC 35A/230VAC
LEAKAGE CURRENT <1mA / 240VAC